Solving common problems in CEMS tracing lines

Solving common problems in CEMS tracing lines

  • Categories:Information Center
  • Author:Baisirui (Hebei) Electric Heat Tracing Co.
  • Origin:
  • Time of issue:2021-11-02 15:17
  • Views:

(Summary description)CEMS tracer lines are suitable for collecting and discharging sampling and measuring flue gas. Coal produces SO2, NO, CO and other gases in the process of use. During the mining process, the flue gas temperature starts to drop, the steam in the flue gas condenses into water, and SO2 starts to react with water to form sulfite. The presence of moisture in the pipe affects the measurement accuracy and instrument life. Therefore, in order to prevent the vapor in the flue gas from condensing, it is necessary to ensure that the temperature is higher than the condensation point. In order to avoid the condensation of steam in the sampling tube into water, it is necessary to carry out heat tracing together with the heat tape, how to control the sampling tube combined with the heat tape.

Solving common problems in CEMS tracing lines

(Summary description)CEMS tracer lines are suitable for collecting and discharging sampling and measuring flue gas. Coal produces SO2, NO, CO and other gases in the process of use. During the mining process, the flue gas temperature starts to drop, the steam in the flue gas condenses into water, and SO2 starts to react with water to form sulfite. The presence of moisture in the pipe affects the measurement accuracy and instrument life. Therefore, in order to prevent the vapor in the flue gas from condensing, it is necessary to ensure that the temperature is higher than the condensation point. In order to avoid the condensation of steam in the sampling tube into water, it is necessary to carry out heat tracing together with the heat tape, how to control the sampling tube combined with the heat tape.

  • Categories:Information Center
  • Author:Baisirui (Hebei) Electric Heat Tracing Co.
  • Origin:
  • Time of issue:2021-11-02 15:17
  • Views:
Information

Solving common problems with CEMS tracer lines.

CEMS tracer lines are suitable for collecting and discharging sampling and measuring flue gas. Coal produces SO2, NO, CO and other gases in the process of use. During the mining process, the flue gas temperature starts to drop, the steam in the flue gas condenses into water, and SO2 starts to react with water to form sulfite. The presence of moisture in the pipe affects the measurement accuracy and instrument life. Therefore, in order to prevent the vapor in the flue gas from condensing, it is necessary to ensure that the temperature is higher than the condensation point. In order to avoid the condensation of steam in the sampling tube into water, it is necessary to carry out heat tracing together with the heat tape, how to control the sampling tube combined with the heat tape.

Single core, double core, combined core can be selected. Heat tracing: automatic power adjustment, automatic compensation, heat tracing and heat preservation, efficient adiabatic.

Electrical control: compensation cable and control cable meet the instrument display monitoring requirements, for the computer centralized control to create the conditions.


Common problems.

1. Heat tracing pipeline does not accompany the heat.

2. The temperature is lower than the dew point, water vapor condensation, sulfur dioxide dissolved, increasing the measurement error, resulting in low measurement results.


Test method: 1.

1. Observe the full sequence of accompanying heat of the accompanying heat pipeline.

2. Touch the accompanying heat pipeline by hand and observe the part of abnormal temperature.

3. Test both ends of the tracing line, whether the power CEMS tracing line is reserved for 1 meter tracing tape.

4. Check the probe heating temperature (temperature display instrument beside the sampling probe or in the analyzer cabinet), the general heating temperature is not less than 160℃.

5. Check the heating temperature of the CEMS tracing line (temperature display instrument in the analyzer cabinet), the general heating temperature is not less than 120℃.

Keyword:

Related Information

Baisirui (Hebei) Electric Heat Tracing Co.

Contact information

Add: North of Yuanda Line, Yuansi County, Shijiazhuang City, Hebei Province, China
Tel:
15733106999 
Company email: baisirui777@sina.com

佰斯锐(河北)电伴热管缆有限公司

Swipe to follow the official information

All rights reserved:Baisirui (Hebei) Electric Heat Tracing Co.        京ICP备17017650XX号待补充         Website:300.cn   Beijing